FEMA Thomasville Federal Regional Center Uninterruptable Power Supply Inspections

Details

Solicitation ID 70FBR425Q00000153
Posted Date 08 Jul 2025 at 4 PM
Response Date 11 Jul 2025 at 6 PM
NAICS Category
Product Service Code
Set Aside No Set-Aside Used
Contracting Office Region 4: Emergency Preparedness An
Agency Department Of Homeland Security
Location Thomasville Georgia United states 31792

Possible Bidders

Miscellaneous Foreign Contractors

Frankfurt am main Isando Washington Arlington

Ww Grainger Incorporated

Cleveland Anchorage Lake forest Boston Atlanta Chula vista Saint louis Niles

Sign up to access Documents

Signup now

The Purpose of this Firm Fixed Price (FFP) Solicitation is to procure Annual Uninterruptable Power Supply (UPS) Inspections, (1) Major PM inspection and (1) Minor PM inspection to ensure that the equipment is in good working condition to maintain clean power to critical loads in the server room at the FEMA Federal Regional Center (FRC) Thomasville, GA Facility.

SCOPE OF WORK
Annual and Semi-Annual UPS Inspections at FEMA Thomasville FRC

UNIT SPECIFICATIONS

• Make: ABB

• Model: Series SG

• Serial Number: P00802820B270R

• kVA/Capacity: 80KVA SG UPS

• Type of batteries:  VRLA

• Number of batteries: 40 batteries (1 Cabinet Sprinter next, AH Capacity – 87, Runtime 365  Model Number -S12v325fl)


Annual System Checks (Major)
• Thermal scan of all power connections Tighten loose connections.
• Check converter & inverter transfer operation.
• Place critical load on maintenance bypass if applicable Exercise external maintenance bypass breakers, if applicable AC input failure test - battery operation, with customer approval.
• Test and confirm Maintenance Bypass Switch operability.
• Place UPS back in service to support critical load.


*Annual System Checks (MAJOR)-Battery System:
• Measure and record all inter-cell and main terminal cable ohmic values.
• Take apart and clean any connection with ohmic value less than the manufacturer’s recommended value or has a value that decreased by more than 20 % below the baseline value. Retorque any connections that are below the battery manufacturer’s recommended value. Requires DC breaker to be opened or UPS charger to be off (Contingent upon customer approval).
* Includes labor and mobilization. No parts included.
*The services performed are designed to meet or exceed IEEE Standard and Battery Manufacturer's Recommendations.


Semi Annual Checks (Minor)
• Check if ambient temperature and humidity is within the correct operating range.
Clearances
• Verify unit has proper clearance for ventilation and service purposes.
Installation.
• Verify the unit is installed in a stable, level and upright position free of vibration.
Application
• Confirm proper UPS application.
Location
• Evaluate the UPS location and determine if it is in accordance with the manual.
Visual Inspection Check Structure.
• Paint- Evaluate for missing paint, unevenness, peeling, cracks and/or dirt.
• Frame- Evaluate for bends, cracks, rust, dirt, welds, and/or parts alignment
• Covers- Evaluate for bends, dirt, stability, and/or gaps
• Accessories- Check caster positions and all labels are applied Assembly
• Screws are secure- Confirm that all screws are secure
• Broken or alien parts- Check for broken or alien parts
• Connectors and wires condition- Evaluate the condition of the connectors and wires
• Edge guards secure- Confirm that all edge guards are secure
• Fast-on lugs secure- Confirm that fast-on lugs are secure Wires Route
• Clearance- Confirm that the wire route clearances are within spec
• PCB connections- Confirm that the wire route PCB connections are within spec Ratings and settings
• Dip switch setting- Verify proper dip switch settings for PCBs
• Unit’s rating- Verify proper unit and/or battery cabinet ratings with sales order Post Operation Checks


Unit Clean Up


• Remove all excess dust and/or dirt internally or externally
• Customer Service Explanation- Prepare and give final report to customer and explain work performed
• Work Request- Schedule next PM or repair work that may need to be performed
does not include replacement parts.
• Replacement parts & labor are at time & material cost + 15%
Conditions – All personnel are subject to completing a successful background check prior to being allowed to conduct any work on the premises.


Location of Required Services
FEMA Thomasville FRC
436 S. Pinetree Blvd.
Thomasville, GA. 31792

Similar Awards

Location Unknown 12 Jun 2012 at 6 PM
Houston Texas 11 Sep 2015 at 6 PM
Lakehurst New jersey 30 Sep 2008 at 6 PM
Location Unknown 12 Apr 2016 at 8 PM
Eglin air force base Florida 27 Jul 2010 at 8 PM