All specifications from the questions and answers has been incorporated to the new specifications. The major change is to the fuel tank size.
CLIN 0001- 30 KW backup generator- 1 EACH
Specifications:
-Minimum 30KW 3 phase (120/208v) 60hz, 38 kva backup generator.
-Generator must run on diesel, have electric start, a block heater, silencer, a trickle charger for the generator batteries, meet EPA UL2200 emissions standards, be UL listed, and be liquid cooled.
-Must have a skid mounted outdoor waterproof enclosure suitable for both high and low temperatures.
-The enclosure must have interior lighting.
-The enclosure must allow operation in all-weather conditions without a separate covering.
- The fuel tank must allow for 72 hours of continuous use at 75% load and be a UL142 Certified double wall tank.
CLIN 0001-30KW GENERATOR 1 EA Total $ _____
CLIN 0002- Automatic Transfer Switch (ATS) 1 EACH
Specifications:
-The ATS must be able to handle 150 Amps service, 4 pole, be in an
outdoor cold weather enclosure, be UL listed, have NFPA 700 and
NFPA 110 emergency code capability, and be compatible with the
generator offered in CLIN 0001.
CLIN 0002 ATS 1 EA TOTAL $ _______