Brand Name APC Smart-UPS RT 5000VA RM 208V to 208/120 SURTD5000RMXLP3U or Equal
Smart UPS Rack Mounted Network UPS/Power Conditioner/Surge Suppressor (Qnty. 6)
UPS must have the following minimum runtimes for the number of watts used:
Watts
Runtime
200 watts
182 minutes
500 watts
76 minutes
700 watts
54 minutes
900 watts
40 minutes
1000 watts
36 minutes
1300 watts
26 minutes
1600 watts
20 minutes
2000 watts
15 minutes
2500 watts
11 minutes
3000 watts
8 minutes
3400 watts
7 minutes
4000 watts
5 minutes
Must have built in power conditioning to protect devices from surges, spikes, lightning and noise to include when connected to generator. Must provide reliable use during unstable and severe power conditions.
Must have minimum of 6 battery and surge protected outlets
Must have built in Test Button on front of unit
Must have resettable circuit breaker
Must have ethernet, USB and Serial connections that allow for network management
Must have Temperature compensated Battery charging
Must have auto restart after UPS Shutdown
Must have input power factor correction
Must be Generator Compatible
Must be Cold Start Capable if complete power outage occurs
Must be Safety Agency Approved
Must have built in Frequency and Voltage Regulation
Must have 208V nominal input voltage and support simultaneous dual 120V/208V output voltage
Must have multiple output voltages to power equipment in cabinet to include 48Vdc, 24Vdc and 120Vac
Must have scalable, uninterrupted runtime Power
Must have serial port
Must have audible alarms
Must have disconnected battery notification
Must have automatic self-test
Must provide predictive failure notification
Must have SmartSlot that allows for customization of UPS with management cards
Must be able to hot-swap batteries (plug and play) with unit plugged in
Must have Flash Upgradable Firmware
Must have minimum 16 segment LED display with easy integrated indicators
Must have pure sine wave output while on battery to ensure compatibility with Power Factor Corrected Services and Sensitive Electronics
Must have preinstalled and operational network management card installed and tested/operational by manufacturer of device AP9631 SmartSlot Network Management Card which enables UPS management and environment monitoring -both temperature and humidity control with system connect to the network. Must have minimum ability of eight users accessing system simultaneously via web browser. Must have minimum ability for three individuals to access network command line interface simultaneously. Must be compatible with PowerChute Software. Built Card must have ethernet, USB (qty 2) and Serial connections that allow for network management. Card must be capable of operating on network using IPv6 protocol. Card must feature device encryption to securely connect via HTTPS/SSL, SSH up to 2048 bit encryption and SNMPV3. Built in card must monitor temperature and humidity and provide reports to end user when it goes out of set ranges. Enviro controls must be able to be monitored remotely. Must be capable of operating on network using IPv6 protocol. Card must feature device encryption to securely connect via HTTPS/SSL, SSH up to 2048 bit encryption and SNMPV3. Card must have RADIUS support. Card must have SMTP Authentication SSL/TLS. Card must have FTP, CLI and TELNET access support. Card must have secure SSH and HTTPS access. Card must have SNMP v1,v2, v3 support. Card must be able to help identify problematic trends/issues through data and event logging.
UPS System must have intelligent self-battery management which conducts automatic self-tests periodically. Tests must assess current battery conditions and also notify users of batteries need replacements.
Must be compatible with PowerChute Network Shutdown Software
Must have Rack Mounted Support Rails
Must include all hardware for rack mounting
Must have Smart-UPS Signaling RS-232 Cable
Must come with USB Cable
Must Come with User Manual
Input Connection NEMA L14-30P
Output Connection: NEMA 5-20R, NEMA L14-30R, NEMA L6-30R
Warranty: Minimum of two year warranty
Smart UPS Rack Mounted Network UPS/Power Conditioner/Surge Suppressor Integrated Network Card
Must be compatible with above salient characteristics/Smart UPS unit - APC
Must be compatible with PowerChute Software
Must have ethernet, two USB connections and an RS 232 Serial connection that allow for network management
Must be capable of operating on network using IPv6 protocol
Must feature device encryption to securely connect via HTTPS/SSL, SSH up to 2048 bit encryption and SNMPV3
Must have RADIUS support
Must have SMTP Authentication SSL/TLS
Must have FTP, CLI and TELNET access support
Must have secure SSH and HTTPS access
Must have SNMP v1,v2, v3 support
Must be able to help identify problematic trends/issues through data and event logging.
Must have minimum ability of eight users accessing system simultaneously via web browser. Must have minimum ability for three individuals to access network command line interface simultaneously.
Must be able to remotely and seamlessly update UPS firmware via web browser interface.
Must be able to remotely reboot equipment and be able to manage device remotely
Must be browser accessible
Must have remote fault notification and be enterprise management system compatible
Must have password security
Must have user manual
Warranty: Minimum 2-year warranty
Bid Protests Not Available