Federal Bid

Last Updated on 10 Nov 2020 at 3 PM
Combined Synopsis/Solicitation
Mcalester Oklahoma

PRE-FAB BUILDING

Solicitation ID W44W9M-21-Q-0012
Posted Date 10 Nov 2020 at 3 PM
Archive Date 02 Dec 2020 at 5 AM
NAICS Category
Product Service Code
Set Aside Total Small Business (SBA) Set-Aside (FAR 19.5)
Contracting Office Usa Osc Mcalester Army Ammo Plnt
Agency Department Of Defense
Location Mcalester Oklahoma United states 74501

The Concrete Shelter proposed will be standard construction featuring solid concrete design with 4" walls and steel rebar reinforced high strength concrete. The standard exterior finish is exposed aggregate, GREYSTONE GRAY.

Concrete Shelter has been designed to be, Bulletproof to 30.06 Rifle from 15 feet per UL-752, provide 2-Hour Fire Rating per UBC, and be Virtually Waterproof and Maintenance Free.

The Shelter you requested will be equipped as follows:

  1. 11’8” WOD x 16’ LOD x 11’1” HOD Concrete Shelter
    10’7” WID x 14’11” LOD x 9’9” HID

    **** Manufactured in a NPCA Certified Factory ****
    Estimated Weight:  50,000 lbs.
    Exterior Finish – Exposed Aggregate Greystone Gray
    Four (4) Cast-in Lift Shackles
    Internal (Non-Exposed) Structural Seals
    1/4” per Foot Roof Slope in All Four Directions with Rubber Membrane Secondary Roof Seal and 2” Roof Overhang on all Four Sides
    150 PSF Floor Load Uniformly Distributed
    60 PSF Roof Load Uniformly Distributed
    150 MPH Wind Load
    Seismic Rated – Category D
  2. Interior Finish
    3/4” Thick White HDPE Coated Plywood Paneling Walls and Ceiling
    Commercial Grade Vinyl Tiled Concrete Floor with Rubber Cove Molding
  3. Insulation
    R-11 Floor and Walls
    R-19 Ceiling
  4. Doors and Accessories
    One (1) 3’ x 7’ Exterior 18 Gauge Galvanized and Painted Steel Door with Cast-in 16 Gauge Galvanized and Painted Steel Door Frame
    with,
    NRP Non-Corrosive Hinges
    Lever Mortise Lockset with Deadbolt and Removable Core
    Aluminum Threshold and Door Sweep
    Weather-stripping
    Hydraulic Door Closer with Hold Open Feature
    Aluminum Drip Shield
  5. Electrical System
    A)      20 Circuit AC Load Center
              120/240 VAC Single Phase
              60 Hz Operation
              100 Amp Main Breaker
    B)      Four (4) Dual Strip LED Interior Light Fixtures with Switch and Lenses
    C)      Two (2) Duplex Convenience Receptacles – Wall Mounted
    D)      Required Surface Mounted EMT Conduit, Connectors, Clamps, Breakers,
              and Wire
  6. Cooling / Heating
    One (1) Mitsubishi Model #PKA-A36KA6, 34,200 BTU Cooling, 37,000 BTU Heating Mini-split Heat Pump System Comprised of One (1) Indoor Wall Mounted Air Handler and One (1) Model #PUZ-A36NHA6 Slim Outdoor Unit with Thermostat Controls
  7. Wall Penetrations
    To be Cored on Site by Others
Bid Protests Not Available

Similar Past Bids

Georgia Not Specified
Location Unknown 02 Apr 2019 at 8 PM
Maryland Not Specified
Fort polk Louisiana 21 Feb 2020 at 9 PM
Location Unknown 10 May 2012 at 3 PM

Similar Opportunities

Lakewood Colorado 25 Jul 2025 at 2 PM
Loveland Colorado 08 Aug 2025 at 8 PM
Randolph air force base Texas 31 Jul 2025 at 7 PM
Location Unknown 14 Nov 2025 at 3 PM
Lakehurst New jersey 15 Jul 2025 at 8 PM